Products | Integrated Control Equipment CK-3380 | |||
|
||||||
Product Detail |
Integrated control equipment CK-3380 is a multi-function control equipment which is used in UniGear 、Handcart Switchgear、Fixation Switchgear、Safe Ring Switchgear and other switchgear .The functions of the equipment are as follows: electriferous state indication/locking 、 temp-humidity intelligent control、breaker state indication、 energy storage state indication、earthing switch status indication、handcart position indication、remote/local operation mode and switch on/off operation |
Features |
High reliability and long service life | The live display/locking function carries two sets of output relays |
Adopting low capacity sensors, the output current is much smaller than the human safety current, with high safety performance | Friendly human-machine interface |
High reliability、long life | With two sets of output relay for electriferous state indication and locking function |
LCD displays the temperature and humidity numerical values | Modbus-RTU |
Two channels of temperature and humidity control | With a key for switch on/off operation (optional) |
The temperature measurement module adopts CT power supply method |
Technical Parameters |
Control part | Fan start condition Temperature>setting upper limit |
Temperature range -9'C~+99C 土1'C | Fan stop condition ? Temperature<setting lower limit |
Humidity range ? 0%RH~99SRH +5sRH | Temperature Setting value ? 3C~40'C |
Heating start condition Temperature<setting lower limit ; Humidity> setting upper limit temperature |
Humidity setting value 40%~-90%RH |
Heating stop condition Temperature>setting lower limit ; Humidity< setting upper limit temperature |
Contact output capacitance 8A, 250V AC/24V DC |
Display Part | |
Threshold voltage ? 15%~40%Un | Auxiliary contact capacitance ? ?5A, 250V AC/30V DC |
Rated frequency ? 50Hz or 60Hz | Locking control trigger voltage 15%~40%Un |
Ambient Temperature -25'C~+55'C | Power supply ? ?110/220V AC |
Ambient Humidity <90%RH | Rated power ? ?≤15W |
Withstand voltage 2kV/1min | Cutting size(mm) 220X165mm? |
Rated power 100-240V AC/DC | Communication Modbus-RTU |
Related Products |
|